FEATURES:
Voltage:85 to 140 Vac 1 phase 2 wire
Frequency:50/60 Hz (Potentiometer setting)Excitation Output:
63 Vdc @ 120 Vac single phase
continuous 5A Max. 110 Vdc 5A for 10 secondsExcitation Resistance:Min. 18 ohms Max. 100 ohmsFuse Spec:Slow blow 5 x 20 mm 8AExternal Volts Adjustment :+/-14% with 1 kΩ 1 watt trimmer
Build Up Voltage:Residual volts at power input terminal > 5 Vac 25 Hz
Soft Start Ramp Time:3 seconds +/-10%
Volts Regulation:< +/-0.5% (with 4% engine governing)
Response Time:< 20 milliseconds
Static Power Dissipation:Max. 4 watts
50 Hz system presets knee point at 48 Hz
60 Hz system presets knee point at 58 HzOver Excitation Current Limiting:Excitation Current 5A +/-10%
Voltage Thermal Drift:< 3% at -40 to +70 °C
Under Frequency Knee Point Thermal Drift:< +/-0.1 Hz at -40 to +70 °C
Environment:
Operating Temperature:-40 to +70 °C
Storage Temperature:-40 to +85 °C
Relative Humidity:Max. 95%
Vibration:5.5Gs @ 60 Hz