SpecificationAmperage : 60 amps
Brand : ATO.COM
BulletPoint1 : 【Specification】 Capacity: 15 hp (11 kw), Input Voltage Three-phase 240v AC±15%(Optional), 240v Input-Current: 45 amps
BulletPoint2 : 【Function】Make AC motor in soft start & soft stop, protecting AC motor from over-voltage, over-current and phase unbalance etc.
BulletPoint3 : 【Protective Function】Input open phase protection, Output open phase protection, Running overload protection etc.
BulletPoint4 : 【Adaptive Motor】Squirrel-cage three-phase asynchronous motor
BulletPoint5 : 【Customer First 】We have soft starters available for other input voltages such as 220V/400V/480V, etc. If you need to purchase the voltage not listed, or have any issue about the product, please email us. We will answer you within 12h
CompatibleDevices : Car
CurrentRating : 500 amps
ExternallyAssignedProductIdentifier : 00852966007292
ExternallyAssignedProductIdentifier1 : 0783902770461
ExternallyAssignedProductIdentifier2 : 783902770461
ItemDisplayDimensions_Length : 2 inches
ItemDisplayWeight : 5 ounces
ItemName : ATO 15 hp 11 kw Soft Starter, 45A AC Motor Starter, 3 Phase 240V, with RS485 Communication Interface, Soft Starter for Three Phase Electric Motor
ItemTypeKeyword : electric-motor-controls
Manufacturer : ATO
Material : Copper
MaximumSwitchingVoltage : 48 volts
MeasurementSystem : Metric
MountingType : Pole
NumberOfItems : 1
OperationMode : Motor
PartNumber : DCCON-C500
PhaseType : 3 phase,three phase,three-phase
ProductDescription :
Specifications:
Capacity 10 hp (7.5 kw)/15 hp (11 kw)/20 hp (15 kw)/25 hp (18 kw)/30 hp (22 kw)/40 hp (30 kw) (Optional)
Weight 5 kgs
Dimension 270*146*160 mm
Input Voltage Three-phase 240v AC
Adaptive Motor Squirrel-cage three-phase asynchronous motor
Starting Times It is recommended not to exceed 20 times per hour.
485 Communication DB9 interface, male plug, ① is RS485+, ⑥ is RS485-
Control Mode:
Operation panel control
Operation panel + external control
External control
External control + COM control
Operation panel + external + COM control
Operation panel + COM control
COM control
No start or stop operation.
Start Mode:
Current-limiting to start.
Voltage ramp to start.
Torque control + current-limiting to start.
Torque control + voltage ramp to start.
Current ramp to start.
Voltage current-limiting double closed-loop start.
Stop Mode
Soft stop.
Free stop.
Protective Function:
Open loop protection for external instantaneous stop terminals.
Over-heat protection for soft starter.
Protection for too long starting time.
Input open phase protection.
Output open phase protection.
Unbalanced three-phase protection.
Starting over current protection.
Running overload protection.
Under voltage protection for power voltage.
Overvoltage protection for power voltage.
Protection for fault parameter setting of the soft starter.
Load short circuit protection.
Auto restart or incorrect wiring protection.
Incorrect wiring protection of external control stop terminals.
Structure
Enclosure IP 20
Cooling Natural wind cooling.
ProductSiteLaunchDate : 2020-07-02T13:02:34.868Z
Size : 15 hp 11 kw
SpecificationMet : Ms
UnspscCode : 39121521
Voltage : 240 volts
Wattage : 11 kilowatts